Boilers | Biomass Boilers | Hurst Boiler

Hurst Boiler CAD Data

View and download select CAD files, 3D drawings and Revit models of Hurst Boiler Models.

Dimensions subject to change without notice. Certified drawings available upon request.

Do not use for construction.

Updating 3D model please wait...

Series 400: S400-4S-0300-0015

Request Quote Quantity

Image Image 2

Product Details

Series 400, 3 Pass Wet Back Scotch Marine Boiler 15 PSI

Boiler Type Steam
Heating Surface (sq ft) 1,500
Steam Output (LBS/HR) 1,035
Gross Output (MBH) 10,043
Firing Rate Gas (1,000 BTU/CF) 12,600.0
Firing Rate LP Gas (91,500 BTU) 138.0
Firing Rate Oil #2 (140,000 BTU) 90.0
Firing Rate Oil #5 & #6 (150,000 BTU) 84.0
(A) *Note: 2 Steam Outlet Size (in) 10
(B) *Note: 2 Water Supply Size (in) 10
(C) *Note: 2 Water Return Size (in) 8.0
(D) Feedwater Connection Size (in) 2.00
(E) Blowdown Connection (Btm) (High Pressure) (in) 1.5
(E) Blowdown Connection (Btm) (Low Pressure & Hw) (in) 2
(H) Shell Inside Diameter (in) 84.0
(G) Furnace O.D. (in) 34.00
(N) Shell To Floor (in) 18.0
(P) Stack Outlet Height (in) 108.750
(O) Skid Length (in) 180.0
(M) Skid To Front Plate (in) 30.6250
(J) Width Without Trim (in) 90.750
(K) Width With Standard Trim (in) 103.00
(F) Stack Outlet Size O.D. (in) 20
(I) Supply Height (in) 108.750
(L) Skid Width (in) 64
(Q) Blowdown Location (in) 33 7/8-98
(R) Steam Outlet Location (in) 69.3750
(S) Supply Location (in) 50.3750
(T) Return Location (in) 140.375
(U) Burner Projection (in) 46.0
(V) Tube Removal (in) 150
(W) Stack Outlet Location (in) 188.8750
(X) Approx. Overall Length (in) 25,800.000
(Y) Center Line Of Furnace (in) 41.0000
Approximate Shipping Weight (lbs) 27100
Water Capacity-Steam (gals) 1,773
Water Capacity-Water (gals) 2,176
100 Boilermaker Lane
Coolidge, GA, United States 31738-0530
Phone: 229-346-3545
Fax: 229-346-3874
info@hurstboiler.com